Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Block MEASURED VARIABLES
Endress+Hauser 11
3.1.2 Function group ADDITIONAL VALUES
MEASURED
VARIABLES
A
⇒
MEASURING VALUES AAA
⇒
MAIN VALUES 000
⇓
ADDITIONAL VALUES 002
Function description
MEASURED VARIABLES → MEASURING VALUES → ADDITIONAL VALUES
TARGET
MASS FLOW
(0020)
! Note!
This function is not available unless one of the following was selected:
• In the DENSITY FUNCTION function (7000):
– % MASS / % VOLUME
– FLEXIBLE and in the MODE function (7021) the option % MASS 2D or % MASS 3D.
Use this function to display the currently measured mass flow of the target fluid.
Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
% TARGET
MASS FLOW
(0021)
! Note!
This function is not available unless one of the following was selected:
• In the DENSITY FUNCTION function (7000):
– % MASS / % VOLUME
– FLEXIBLE and in the MODE function (7021) the option % MASS 2D or % MASS 3D.
In this function, the currently measured mass flow of the target fluid is displayed as a %
(of the overall mass flow). Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
TARGET
VOLUME FLOW
(0022)
! Note!
This function is not available unless one of the following was selected:
• In the DENSITY FUNCTION function (7000):
– % MASS / % VOLUME
– FLEXIBLE and in the MODE function (7010) the option % VOLUME 2D or
% VOLUME 3D.
In this function, the currently measured volume flow of the target fluid is displayed.
Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
% TARGET
VOLUME FLOW
(0023)
! Note!
This function is not available unless one of the following was selected:
• In the DENSITY FUNCTION function (7000):
– % MASS / % VOLUME
– FLEXIBLE and in the MODE function (7010) the option % VOLUME 2D or
% VOLUME 3D.
Use this function to display the currently measured volume flow of the target fluid as a %
(of the overall volume flow). Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign