Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 169
3.9 "Advanced Diagnostics" Transducer Block parameters
!
Note!
The parameters of the "Advanced Diagnostics" Transducer Block are ready for use and can be
configured if the "Advanced Diagnostics" add-on is installed in the measuring device (order option).
Otherwise the value "NaN" (not-a-number) or "Not licensed" is displayed in a parameter.
The following table shows the Endress+Hauser-specific parameters of the "Advanced Diagnostics"
Transducer Block. These can only be changed after entering a release code in the "Access - Code"
parameter.
!
Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: → www.endress.com → download).
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Access - Code AUTO - OOS All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
• Code 83 (factory setting)
•Personal code ( → Page 135)
User input:
Max. 4-digit number (0 to 9999)
! Note!
• If the write protection is enabled then access to the manufacturer-specific
parameters is blocked even if the right code is entered. Write protection
can be activated and deactivated by means of jumpers on the I/O board
(→ See Operating Instructions for Proline Promass 83 FOUNDATION
Fieldbus, BA065D).
• You can disable programming again by entering any number (other than
the release code) in this parameter.
• The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
• Certain parameters are not accessible unless a special
service code is entered. This service code is known only to the
Endress+Hauser service organization. Please contact your
Endress+Hauser service center if you require clarification.
• The entry made here does not affect the local display. Programming via
the function matrix thus has to be enabled separately.
Access - Status read only Use this parameter to display the current status of the possibilities for
accessing the manufacturer-specific parameters of the device.
Display:
• LOCKED (parameterization disabled)
• ACCESS CUSTOMER (parameterization enabled)
• ACCESS SERVICE (parameterization enabled, access to service level)