6 Block TOTALIZER Device Functions Proline Promass 83 FOUNDATION Fieldbus
44 Endress+Hauser
6.1 Group TOTALIZERS (1 to 3)
6.1.1 Function group CONFIGURATION
TOTALIZER D
⇒
TOTALIZER 1 DAA
⇒
CONFIGURATION 300
⇓
TOTALIZER 2 DAB
⇒
CONFIGURATION 300
⇓
TOTALIZER 3 DAC
⇒
CONFIGURATION 300
Function description
TOTALIZER → TOTALIZERS (1 to 3) → CONFIGURATION
The function descriptions below apply to totalizers 1 to 3; the totalizers are independently configurable.
ASSIGN
(3000)
Use this function to assign a measured variable to the totalizer.
Options (standard):
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
Advanced options with optional software package CONCENTRATION:
TARGET MASS FLOW
TARGET VOLUME FLOW
CORRECTED TARGET VOLUME FLOW
CARRIER MASS FLOW
CARRIER VOLUME FLOW
CORRECTED CARRIER VOLUME FLOW
Factory setting:
MASS FLOW
! Note!
• The totalizer is reset to "0" as soon as the selection is changed.
• If you select OFF, the ASSIGN function (3000) is the only function shown in the
CONFIGURATION function group of the totalizer in question.