8 Block SPECIAL FUNCTION Device Functions Proline Promass 83 FOUNDATION Fieldbus
74 Endress+Hauser
8.2.3 Function group MASS FLOW
SPECIAL FUNCTION H
⇒
DENSITY FUNCTIONS HAA
⇓
ADVANCED DIAGNOSTICS HEA
⇒
CONFIGURATION 740
⇓
ACQUISITION 741
⇓
MASS FLOW 742
Function description
SPECIAL FUNCTION → ADVANCED DIAGNOSTICS → MASS FLOW
! Note!
The appropriate unit is taken from the UNIT MASS FLOW function (0400).
REFERENCE VALUE
MASS FLOW
(7420)
The reference value for the mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
MASS FLOW
(7421)
The measured mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
MINIMUM MASS FLOW
(7422)
The lowest mass flow value since the saved values were last reset appears on the display.
Display:
5-digit floating-point number, including unit and sign
MAXIMUM MASS FLOW
(7423)
The highest mass flow value since the saved values were last reset appears on the display.
Display:
5-digit floating-point number, including unit and sign
HISTORY MASS FLOW
(7424)
The last ten mass flow values since the saved values were last reset appear on the display.
Display:
5-digit floating-point number, including unit and sign
DEVIATION MASS FLOW
(7425)
This function displays the deviation between the measured mass flow and the reference
values (FACTORY or USER) selected in the function SELECT REFERENCE CONDITION
(7402).
Display:
5-digit floating-point number, including unit and sign
WARNING LEVEL
(7426)
! Note!
This function is not available unless ON was selected in the WARNING MODE function
(7403).
Use this function to specify a limit value for the mass flow. A notice message is generated
if the limit value is exceeded.
User input:
0 to 99999 [mass flow unit]
Factory setting:
90000 kg/h