6 Discrete Output function block Device Functions Proline Promass 83 FOUNDATION Fieldbus
190 Endress+Hauser
6.2.4 Values for the parameters CAS_IN_D, RCAS_IN_D, OUT_D,
and SP_D
Via the Discrete Output function block, different instrument functions in the Transducer Block can
be initiated via manufacturer-specific, fixed set point values from an upstream function block.
Here it must be observed that the desired function is only then executed when a status change from
the value 0 (Discrete state 0) to the corresponding function value (following table) takes place. The
value 0 always serves as the starting point for the corresponding control of instrument functions. A
status change from a value not equal to zero to another value has no effect.
Input assignment of the CAS_IN_D, RCAS_IN_D, OUT_D, SP_D parameters
Status changes Action
Discrete state 0 → Discrete state 1 Reserved
Discrete state 0 → Discrete state 2 Positive zero return: ON
Discrete state 0 → Discrete state 3 Positive zero return: OFF
Discrete state 0 → Discrete state 4 Reserved
Discrete state 0 → Discrete state 5 Reserved
Discrete state 0 → Discrete state 6 Reserved
Discrete state 0 → Discrete state 7 Reset totalizers 1, 2, 3
Discrete state 0 → Discrete state 8 Reset totalizer 1
Discrete state 0 → Discrete state 9 Reset totalizer 2
Discrete state 0 → Discrete state 10 Reset totalizer 3
Discrete state 0 → Discrete state 27 Permanent storage: OFF
Discrete state 0 → Discrete state 28 Permanent storage: ON
The following measured variables are available if the "Concentration measurement" add-on is installed in the measuring
device (order option)
Discrete state 0 → Discrete state 60 Select concentration specification 1
Discrete state 0 → Discrete state 61 Select concentration specification 2
Discrete state 0 → Discrete state 62 Select concentration specification 3
Discrete state 0 → Discrete state 63 Select concentration specification 4
The following measured variables are available if the "Advanced diagnostics" add-on is installed in the measuring device
(order option)
Discrete state 0 → Discrete state 25 Advanced diagnostics: Warning mode off
Discrete state 0 → Discrete state 26 Advanced diagnostics: Warning mode on
Discrete state 0 → Discrete state 70 Start determining user reference status
Discrete state 0 → Discrete state 71 Reserved
Discrete state 0 → Discrete state 72 Reserved
Discrete state 0 → Discrete state 73 Reserved
Discrete state 0 → Discrete state 74 Acquisition mode: off
Discrete state 0 → Discrete state 75 Acquisition mode: periodic
Discrete state 0 → Discrete state 76 Acquisition mode: single shot
Discrete state 0 → Discrete state 77 Acquisition mode: reset history
Discrete state 0 → Discrete state 78 Start manual determination of diag. parameter