Device Functions Proline Promass 83 FOUNDATION Fieldbus 7 Block BASIC FUNCTION
Endress+Hauser 49
7.1 Group FOUNDATION FIELDBUS
7.1.1 Function group CONFIGURATION
BASIC FUNCTION G
FOUNDATION FIELDBUS GGA
CONFIGURATION 620
Function description
BASIC FUNCTION FOUNDATION FIELDBUS CONFIGURATION
WRITE PROTECT
(6200)
Use this function to check whether the measuring device can be write accessed via the
fieldbus.
Display:
OFF
Write access via FOUNDATION Fieldbus possible
ON
Write protection via FOUNDATION Fieldbus blocked
Factory setting:
OFF
! Note!
Hardware write protection is activated and deactivated by means of a jumper on the
I/O board (see Operating Instructions for Proline Promass 83 FOUNDATION Fieldbus
BA 065D/06/en).
SIMULATION
(6201)
Use this function to check whether a simulation in the Analog Input function block is
possible.
Display:
OFF
Simulation in the Analog Input and Discrete Output function block is not possible.
ON
Simulation in the Analog Input and Discrete Output function block is possible.
Factory setting:
ON
! Note!
The simulation mode is activated and deactivated by means of a jumper on the
I/O board (see Operating Instruction Proline Promass 83 FOUNDATION Fieldbus
BA065D/06/en).
The status of the simulation mode is also shown in the parameter BLOCK_ERR of
the Resource Block.
DEVICE PD-TAG
(6203)
Use this function to enter a tag name for the measuring device.
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,-, punctuation marks
Factory setting:
E+H_PROMASS_83_XXXXXXXXXXX