Device Functions Proline Promass 83 FOUNDATION Fieldbus 7 Block BASIC FUNCTION
Endress+Hauser 49
7.1 Group FOUNDATION FIELDBUS
7.1.1 Function group CONFIGURATION
BASIC FUNCTION G
⇒
FOUNDATION FIELDBUS GGA
⇒
CONFIGURATION 620
Function description
BASIC FUNCTION → FOUNDATION FIELDBUS → CONFIGURATION
WRITE PROTECT
(6200)
Use this function to check whether the measuring device can be write accessed via the
fieldbus.
Display:
OFF
Write access via FOUNDATION Fieldbus possible
ON
Write protection via FOUNDATION Fieldbus blocked
Factory setting:
OFF
! Note!
Hardware write protection is activated and deactivated by means of a jumper on the
I/O board (see Operating Instructions for Proline Promass 83 FOUNDATION Fieldbus
BA 065D/06/en).
SIMULATION
(6201)
Use this function to check whether a simulation in the Analog Input function block is
possible.
Display:
OFF
Simulation in the Analog Input and Discrete Output function block is not possible.
ON
Simulation in the Analog Input and Discrete Output function block is possible.
Factory setting:
ON
! Note!
• The simulation mode is activated and deactivated by means of a jumper on the
I/O board (see Operating Instruction Proline Promass 83 FOUNDATION Fieldbus
BA065D/06/en).
• The status of the simulation mode is also shown in the parameter BLOCK_ERR of
the Resource Block.
DEVICE PD-TAG
(6203)
Use this function to enter a tag name for the measuring device.
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,-, punctuation marks
Factory setting:
E+H_PROMASS_83_XXXXXXXXXXX