EasyManua.ls Logo

Endress+Hauser Proline Promass 83 - Totalizer Transducer Block parameters

Endress+Hauser Proline Promass 83
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 151
3.6 "Totalizer" Transducer Block parameters
The following table shows the Endress+Hauser-specific parameters of the "Totalizer" Transducer
Block. These can only be changed after entering a release code in the "Access - Code" parameter.
!
Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Totalizer" Transducer Block/base index 1900
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Access - Code AUTO - OOS All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 83 (factory setting)
•Personal code (Page 135)
User input:
Max. 4-digit number (0 to 9999)
! Note!
If the write protection is enabled then access to the manufacturer-specific
parameters is blocked even if the right code is entered. Write protection
can be activated and deactivated by means of jumpers on the I/O board
(See Operating Instructions for Proline Promass 83 FOUNDATION
Fieldbus, BA065D).
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
The entry made here does not affect the local display. Programming via
the function matrix thus has to be enabled separately.
Access - Status read only Use this parameter to display the current status of the possibilities for
accessing the manufacturer-specific parameters of the device.
Display:
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled, access to service level)

Table of Contents

Other manuals for Endress+Hauser Proline Promass 83

Related product manuals