3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
152 Endress+Hauser
Tot. 1 to 3 - Sum AUTO - OOS Use this parameter to view the total for the totalizer’s measured variable
aggregated since measuring commenced. The value can be positive or
negative, depending on the setting selected in the parameter
"Tot. 1 to 3 - Mode" (Page 153) and the direction of flow.
Display:
Max. 7-digit floating-point number, including unit and sign
(e.g. 15467.04 m
3
; –4925.631 kg)
! Note!
The effect of the setting in the parameter "Tot. 1 to 3 - Mode"
is as follows:
If the setting is BALANCE, the totalizer balances flow in the positive
and negative directions.
If the setting is FORWARD, the totalizer registers only flow in the
positive direction.
If the setting is REVERSE, the totalizer registers only flow in the
negative direction.
The totalizers' response to faults is defined in the parameter
"Tot. - Failsafe All".
Tot. 1 to 3 - Unit AUTO - OOS Use this parameter to define the unit for the totalizer's measured variable, as
selected beforehand.
Options: (for the MASS FLOW assignment):
Metric g; kg; t
US oz; lb; ton
Factory setting:
Depends on nominal diameter and country Page 193 ff.
Options (for the VOLUME FLOW assignment):
Metric cm
3
; dm
3
; m
3
; ml; l; hl; Ml Mega
US cc; af; ft
3
; oz f; gal; Kgal; Mgal; bbl (normal fluids); bbl (beer);
bbl (petrochemicals); bbl (filling tanks)
Imperial gal; Mgal; bbl (beer); bbl (petrochemicals)
Factory setting:
Depends on nominal diameter and country Page 193 ff.
! Note!
The unit selected here does not have any effect on the desired volume unit
which should be transmitted by means of the FOUNDATION Fieldbus
interface. This setting is made separately by means of the corresponding AI
Block in the XD_SCALE parameter group.
"Totalizer" Transducer Block/base index 1900
Parameter
Write access
with operating
mode
(MODE_BLK)
Description