Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 153
Tot. 1 to 3 - Assign AUTO - OOS Use this parameter to assign a measured variable to the totalizer.
Options:
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
Factory setting:
MASS FLOW
Advanced options with optional software package
CONCENTRATION:
TARGET MASS FLOW
TARGET VOLUME FLOW
CORRECTED TARGET VOLUME FLOW
CARRIER MASS FLOW
CARRIER VOLUME FLOW
CORRECTED CARRIER VOLUME FLOW
! Note!
The totalizer is reset to "0" as soon as the selection is changed.
Tot. 1 to 3 - Mode AUTO - OOS Use this parameter to define how the flow components are to be totaled by
the totalizer.
Options:
BALANCE
Positive and negative flow components. The positive and negative flow
components are balanced. In other words, net flow in the flow direction is
registered.
FORWARD
Positive flow components only.
REVERSE
Negative flow components only.
Factory setting:
Totalizer 1 = BALANCE
Totalizer 2 = FORWARD
Totalizer 3 = REVERSE
Tot. 1 to 3 - Reset AUTO - OOS Reset the totalizer ("Tot. 1…3 - Sum" parameter) to zero.
Options:
NO
YES
Factory setting:
NO
! Note!
Also using cyclic data transmission, totalizer resetting can be controlled or
initiated via the Discrete Output function block.
"Totalizer" Transducer Block/base index 1900
Parameter
Write access
with operating
mode
(MODE_BLK)
Description