3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
154 Endress+Hauser
Tot. - Reset All AUTO - OOS Reset all totalizers simultaneously to zero ("Tot. 1 to 3 - Sum" parameter).
Options:
NO
YES
Factory setting:
NO
! Note!
Also using cyclic data transmission, totalizer resetting can be controlled or
initiated via the Discrete Output function block.
Tot. - Failsafe All AUTO - OOS Use this parameter to define the common response of all totalizers (1 to 3) in
case of error.
Options:
STOP
The totalizers are paused until the fault is rectified.
ACTUAL VALUE
The totalizers continue to count based on the current flow measured value.
The fault is ignored.
HOLD VALUE
The totalizers continue to count the flow based on the last valid flow value
(before the fault occurred).
Factory setting:
STOP
Amp. Device Type read only This parameter is only used for service purposes.
"Totalizer" Transducer Block/base index 1900
Parameter
Write access
with operating
mode
(MODE_BLK)
Description