Device Functions Proline Promass 83 FOUNDATION Fieldbus 6 Discrete Output function block
Endress+Hauser 189
of the Discrete Output function block is communicated to the process control system as an answer
message via parameter RCAS_OUT_D.
In the AUTO operating mode (automatic operation), the set point value (parameter SP_D) is
prescribed directly in the Discrete Output function block. In this case, the parameter CAS_IN_D is
not taken into consideration in the internal calculation.
In the MAN operating mode (HAND), the output value (parameter OUT_D) can be prescribed
directly in the Discrete Output function block. No internal calculation takes place.
6.2 Important functions and parameters of the Discrete
Output function block
The most important functions and parameters of the Discrete Output function block are listed below.
!
Note!
All the FOUNDATION Fieldbus parameters available are described in the Operating Instructions
"FOUNDATION Fieldbus Overview" (BA013S) (available at: www.endress.com download).
6.2.1 Selecting the operating mode
The operating mode is configured via the MODE_BLK parameter group. The Discrete Output
function block supports the following operating modes:
•AUTO
MAN
•CAS
•RCAS
•OOS
6.2.2 Safety behavior
There is a safety default available (fault state) for the Discrete Output function block. This is
activated when a fault condition (of the corresponding valid set point value) exists longer than
defined in the parameter FSTATE_TIME, or when the parameter SET_FSTATE in the Resource
Block is activated. The safety operation is determined via the parameters FSTATE_TIME,
FSTATE_VAL_D, and IO_OPTS.
6.2.3 Assignment between the Discrete Output function block
and the Transducer Block
The assignment or connection between the Discrete Output function block and the Transducer
Block takes place in the Discrete Output function block via the parameter CHANNEL.
Parameter CHANNEL 16 (= Discrete Output function block)