8 Block SPECIAL FUNCTION Device Functions Proline Promass 83 FOUNDATION Fieldbus
78 Endress+Hauser
8.2.7 Function group TUBE DAMPING
SPECIAL FUNCTION H
⇒
DENSITY FUNCTIONS HAA
⇓
ADVANCED DIAGNOSTICS HEA
⇒
CONFIGURATION 740
⇓
ACQUISITION 741
⇓
MASS FLOW 742
⇓
DENSITY 743
⇓
REFERENCE DENSITY 744
⇓
TEMPERATURE 745
⇓
TUBE DAMPING 746
Function description
SPECIAL FUNCTION → ADVANCED DIAGNOSTICS → TUBE DAMPING
REFERENCE VALUE
TUBE DAMPING
(7460)
The reference value for tube damping appears on the display.
Display:
5-digit floating-point number
TUBE DAMPING
(7461)
The measured tube damping appears on the display.
Display:
5-digit floating-point number
MINIMUM
TUBE DAMPING
(7462)
The lowest tube damping value since the saved values were last reset appears on the
display.
Display:
5-digit floating-point number
MAXIMUM
TUBE DAMPING
(7463)
The highest tube damping value since the saved values were last reset appears on the
display.
Display:
5-digit floating-point number
HISTORY
TUBE DAMPING
(7464)
The last ten tube damping values since the saved values were last reset appears on the
display.
Display:
5-digit floating-point number
DEVIATION
TUBE DAMPING
(7465)
This function displays the deviation between the measured tube damping and the
reference values (FACTORY or USER) selected in the function SELECT REFERENCE
CONDITION (7402).
Display:
5-digit floating-point number
WARNING LEVEL
(7466)
! Note!
This function is not available unless ON was selected in the WARNING MODE function
(7403).
Use this function to specify a limit value for tube damping. A notice message is generated
if the limit value is exceeded.
User input:
0 to 99999%
Factory setting:
1000%