3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
170 Endress+Hauser
Adv. -
Ref.Cond.User
AUTO - OOS Use this parameter to start determining the user reference status. The
following values are determined:
•MASS FLOW
•DENSITY
•REFERENCE DENSITY
• TEMPERATURE
• TUBE DAMPING
• ELECTRODYNAMIC SENSORS
• OPERATING FREQUENCY FLUCTUATION
• TUBE DAMPING FLUCTUATION
Options:
CANCEL
START
Factory setting:
CANCEL
Adv. - Select
Ref.Condition
AUTO - OOS Use this parameter to select the reference status which should be used to
compare the advanced diagnostics parameters (see parameter
"Adv. - Acquisition Mode" → Page 171).
Options:
FACTORY
USER
Factory setting:
FACTORY
Adv. -
Warning Mode
AUTO - OOS Use this parameter to determine whether a warning should be generated
when there is a deviation between the reference status (FACTORY or USER,
see parameter "Adv. - Select Ref.Condition") and the current measuring
values.
The values of the following parameters are compared to the reference status :
• Mass Flow - Actual Value ( → Page 172)
• Density - Actual Value ( → Page 173)
• Ref.Density - Actual Value ( → Page 174)
• Temperature - Actual Value ( → Page 175)
• Tube Damping - Actual Value ( → Page 176)
• El.Dyn.Sens. - Actual Value ( → Page 177)
• Freq.Fluct. - Actual Value ( → Page 178)
• Tube Damp.Fluct. - Actual Value ( → Page 179)
Options:
OFF
ON
Factory setting:
ON
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description