Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 175
Ref.Density -
Warning Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this parameter to specify a limit value for the reference density. A notice
message is generated if the limit value is exceeded.
User input:
0 to 99999 [%]
Factory setting:
100%
Temperature -
Ref.Value Factory
read only The reference value for the temperature appears on the display.
Display:
5-digit floating-point number, including unit and sign
System Unit
Temperature
AUTO - OOS Use this function to select the unit for displaying the temperature.
The unit you select here is also valid for:
• Simulation
• Reference temperature (for corrected volume measurement with
measured reference density)
Options:
°C (Celsius)
K (Kelvin)
°F (Fahrenheit)
R (Rankine)
Factory setting:
°C
Temperature -
Ref.Value User
read only The reference value for the temperature appears on the display.
Display:
5-digit floating-point number, including unit and sign
Temperature -
Actual Value
read only The currently measured temperature appears on the display.
Display:
5-digit floating-point number, including unit and sign
Temperature -
Min.Value
read only The lowest temperature value since the saved values were last reset appears
on the display.
Display:
5-digit floating-point number, including unit and sign
Temperature -
Max.Value
read only The highest temperature value since the saved values were last reset appears
on the display.
Display:
5-digit floating-point number, including unit and sign
Temperature -
History 1…10
read only The last ten temperature values since the saved values were last reset appear
on the display.
Display:
5-digit floating-point number, including unit and sign
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description