3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
174 Endress+Hauser
Density - Warning
Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this function to specify a limit value for the density. A notice message is
generated if the limit value is exceeded.
User input:
0 to 99999 [%]
Factory setting:
100%
Ref.Density -
Ref.Value Factory
read only The reference value for the reference density appears on the display.
Display:
5-digit floating-point number, incl. units
System Unit -
Ref.Density
AUTO - OOS Use this parameter to select the unit for displaying the reference density.
The unit you select here is also valid for:
• Simulation
• Fixed reference density (for calculation of corrected volume flow)
Options:
Metric → kg/Nm
3
; kg/Nl
US → g/Scc; kg/Sm
3
; lb/Scf
Factory setting:
kg/Nl
Ref.Density -
Ref.Value User
read only The reference value for the reference density appears on the display.
Display:
5-digit floating-point number, incl. units
Ref.Density -
Actual Value
read only The measured reference density appears on the display.
Display:
5-digit floating-point number, incl. units
Ref.Density -
Min. Value
read only The lowest reference density value since the saved values were last reset
appears on the display.
Display:
5-digit floating-point number, incl. units
Ref.Density -
Max.Value
read only The highest reference density value since the saved values were last reset
appears on the display.
Display:
5-digit floating-point number, incl. units
Ref.Density -
History 1…10
read only The last ten reference density values since the saved values were last reset
appear on the display.
Display:
5-digit floating-point number, incl. units
Ref.Density -
Deviation
read only This function displays the deviation between the measured reference density
and the reference values selected in the parameter "Adv. - Select
Ref.Condition" (FACTORY or USER) → Page 170.
Display:
5-digit floating-point number, incl. units
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description