3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
176 Endress+Hauser
Temperature -
Deviation
read only This function displays the deviation between the measured temperature and
the reference values selected in the parameter "Adv. - Select Ref.Condition"
(FACTORY or USER)Page 170.
Display:
5-digit floating-point number, including unit and sign
Temperature -
Warning Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this parameter to specify a limit value for the temperature. A notice
message is generated if the limit value is exceeded.
User input:
0 to 99999 °C
Factory setting:
100 °C
Tube Damping -
Ref.Value Factory
read only The reference value for tube damping appears on the display.
Display:
5-digit floating-point number
Tube Damping -
Ref.Value User
AUTO - OOS The reference value for tube damping appears on the display.
Display:
5-digit floating-point number
Tube Damping -
Actual Value
read only The measured tube damping appears on the display.
Display:
5-digit floating-point number
Tube Damping -
Min.Value
read only The lowest tube damping value since the saved values were last reset
appears on the display.
Display:
5-digit floating-point number
Tube Damping -
Max.Value
read only The highest tube damping value since the saved values were last reset
appears on the display.
Display:
5-digit floating-point number
Tube Damping -
History 1…10
read only The last ten tube damping values since the saved values were last reset
appears on the display.
Display:
5-digit floating-point number
Tube Damping -
Deviation
read only This function displays the deviation between the measured tube damping
and the reference values selected in the parameter "Adv. - Select
Ref.Condition" (FACTORY or USER)Page 170.
Display:
5-digit floating-point number
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description