3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
172 Endress+Hauser
System Unit -
Mass Flow
AUTO - OOS Use this function to select the unit for displaying the mass.
Options:
Metric g; kg; t
US oz; lb; ton
Factory setting:
Depends on country (kg or US-lb)
! Note!
The unit of the totalizers is independent of your choice here. The unit for
each totalizer is selected separately for the totalizer in question.
Mass Flow -
Ref.Value User
read only The reference value for the mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
Actual Value
read only The measured mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
Min.Value
read only The lowest mass flow value since the saved values were last reset appears on
the display.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
Max.Value
read only The highest mass flow value since the saved values were last reset appears
on the display.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
History 1…10
read only The last ten mass flow values since the saved values were last reset appear
on the display.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
Deviation
read only This function displays the deviation between the measured mass flow and
the reference values selected in the parameter "Adv. - Select Ref.Condition"
(FACTORY or USER)Page 170.
Display:
5-digit floating-point number, including unit and sign
Mass Flow -
Warning Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this parameter to specify a limit value for the mass flow. A notice
message is generated if the limit value is exceeded.
User input:
0 to 99999 [mass flow unit]
Factory setting:
90000 kg/h
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description