Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 171
Adv. -
Acquisition Mode
AUTO - OOS Use this parameter to specify whether the advanced diagnostics parameters
should be determined on a periodical or single-shot basis.
Options:
OFF
PERIODICAL
SINGLE SHOT
Factory setting:
OFF
! Note!
See the Chapter on "Commissioning" in the Operating Instructions Proline
Promass 83, BA 065D/06/en for more information on advanced
diagnostics.
Adv. -
Acquisition Period
AUTO - OOS
! Note!
This option is not active unless PERIODICAL was selected in the
parameter "Adv. - Acquisition Mode".
Use this parameter to specify the time interval after which the advanced
diagnostics parameters should be recorded. The time interval starts with the
confirmation of the input.
User input:
0 to 99999 s
Factory setting:
3600 s
! Note!
A reference status must be defined prior to determining the diagnosis
parameters, see parameter "Adv. - Select Ref.Condition".
Adv. -
Acquisition Do
AUTO - OOS
! Note!
This option is not active unless SINGLE SHOT was selected in the
parameter "Adv. - Acquisition Mode".
Use this parameter to start determining the advanced diagnostics parameters
on a single-shot basis.
Options:
CANCEL
START
Factory setting:
CANCEL
! Note!
A reference status must be defined prior to determining the diagnosis
parameters, see parameter "Adv. - Select Ref.Condition".
Adv. - Reset History AUTO - OOS Use this function to delete all history values.
Options:
NO
YES
Factory setting:
NO
Mass Flow -
Ref.Value Factory
read only The reference value for the mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description