3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
178 Endress+Hauser
El.Dyn.Sens. -
Warning Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this parameter to specify a limit value for the electrodynamic sensors.
A notice message is generated if the limit value is exceeded.
User input:
0 to 99999 [%]
Factory setting:
100%
Freq.Fluct. -
Ref.Value Factory
read only The reference value for the fluctuation of the operating frequency appears on
the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Ref.Value User
read only The reference value for the fluctuation of the operating frequency appears on
the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Actual Value
read only The measured fluctuation of the operating frequency appears on the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Min.Value
read only The lowest value of the operating frequency fluctuation since the saved
values were last reset appears on the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Max.Value
read only The highest value of the operating frequency fluctuation since the saved
values were last reset appears on the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
History 1…10
read only The last ten values of the operating frequency fluctuation since the saved
values were last reset appear on the display.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Deviation
read only This function displays the deviation between the measured fluctuation in
operating frequency and the reference values selected in the parameter
"Adv. - Select Ref.Condition" (FACTORY or USER) → Page 170.
Display:
5-digit floating-point number, Hz
Freq.Fluct. -
Warning Level
AUTO - OOS
! Note!
This option is not active unless ON was selected in the parameter
"Adv. - Warning Mode".
Use this function to specify a limit value for the operating frequency
fluctuation. A notice message is generated if the limit value is exceeded.
User input:
0 to 99999 Hz
Factory setting:
1000 Hz
"Advanced Diagnostics" Transducer Block/base index 2200
Parameter
Write access
with operating
mode
(MODE_BLK)
Description