Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 139
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign simulation process variable – Select a process variable for
the simulation process that is
activated.
• Off
• Volume flow
• Mass flow
• Flow velocity
• Sound velocity
• Temperature
*
• Pressure
*
• Density
*
• Reference density
*
• S&W volume flow
*
• GSV flow
*
• NSV flow
*
• API gravity
*
• API slope
*
Off
Process variable value A process variable is selected
in the Assign simulation
process variable parameter
(→ 139).
Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Current output 1 to n simulation – Switch the simulation of the
current output on and off.
• Off
• On
Off
Current output value In the Current output 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA 3.59 mA
Frequency output 1 to n simulation In the Operating mode
parameter, the Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
• Off
• On
Off
Frequency output 1 to n value In the Frequency simulation
1 to n parameter, the On
option is selected.
Enter the frequency value for
the simulation.
0.0 to 12 500.0 Hz 0.0 Hz
Pulse output simulation 1 to n In the Operating mode
parameter, the Pulse option is
selected.
Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
(→ 111) defines the
pulse width of the pulses
output.
• Off
• Fixed value
• Down-counting
value
Off
Pulse value 1 to n In the Pulse output
simulation 1 to n parameter,
the Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65 535 0
Switch output simulation 1 to n In the Operating mode
parameter, the Switch option
is selected.
Switch the simulation of the
switch output on and off.
• Off
• On
Off
Switch state 1 to n – Select the status of the status
output for the simulation.
• Open
• Closed
Open
Relay output 1 to n simulation – Switch simulation of the relay
output on and off.
• Off
• On
Off
Switch state 1 to n The On option is selected in
the Switch output simulation
1 to n parameter parameter.
Select status of the relay
output for the simulation.
• Open
• Closed
Open
Pulse output simulation – Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
defines the pulse width
of the pulses output.
• Off
• Fixed value
• Down-counting
value
Off