9.2.4.1  Gas High Alarm 
1.  In the Hydran 201Ti, access the submenu H201Ti Vx.xx;Relays/Analog.  
2.  Access the submenu Relays/Analog;GasH Relay. 
3.  Set the parameter RelayMode of the Gas High relay to On. 
4.  On the H201Ci-1, verify that:  
•  The door-mounted 1 push-button indicator is lit. 
•  The Alarm 1 (Gas High) indicator (yellow, DS10; item 15 in Figure 4-7) is lit. 
•  The Alarm 1 NO contact is closed. 
•  The Alarm 1 NC contact is open. 
•  Other  LED  indicators  and  contacts  have  not  changed  from  their  previous 
state. 
•  If connected, the supervisory control and data acquisition (SCADA) system has 
detected the alarm.  
Note:  Pushing the 1 push-button to acknowledge the gas alarm condition should not turn 
off the indicator since the condition has not cleared. 
 
9.2.4.2  Gas High-High Alarm 
1.  Access the submenu Relays/Analog;GasHH Relay. 
2.  Set the parameter RelayMode of the Gas High-High relay to On. 
3.  On the H201Ci-1, verify that:  
•  The door-mounted 2 push-button indicator is lit. 
•  The Alarm 2 (Gas High-High) indicator (yellow, DS9; item 14 in Figure 4-7) is lit. 
•  The Alarm 2 NO contact is closed. 
•  The Alarm 2 NC contact is open.  
•  Other  LED  indicators  and  contacts  have  not  changed  from  their  previous 
state. 
•  If connected, the SCADA system has detected the alarm.  
Note:  Pushing the 2 push-button to acknowledge the gas alarm condition should not turn 
off the indicator since the condition has not cleared. 
 
9.2.4.3  System Fault Alarm 
1.  Access submenu Relays/Analog;SysOK Relay. 
2.  Set the parameter RelayMode of the System Fault relay to Off. 
3.  On the H201Ci-1, verify that: 
•  The display goes blank. 
•  The two door-mounted push-button indicators (1 and 2) remain lit. 
•  The System OK indicator (yellow, DS11; item 16 in Figure 4-7) turns off. 
•  The System OK alarm NO contact is open. 
•  The System OK alarm NC contact is closed.