MA-033 Rev. 14.0, 12-Nov-18
The gas alarm indicators (yellow DS9 and DS10) and contacts are restored to
their normal state (no alarm condition).
If connected, the SCADA system has detected the alarm.
Note: Pushing both push-buttons to acknowledge the gas alarm conditions should
turn off the indicators since the conditions are cleared during a system fault.
9.2.4.4 System Fault Alarm Cleared
1. Set the same RelayMode parameter to Normal.
2. On the H201Ci-1, verify that:
The H201Ci-1’s display is functional again.
The two door-mounted push-button indicators (1 and 2) are lit because the
gas alarm conditions still exist.
The System OK indicator (yellow, DS11; item 16 in Figure 4-7) is lit.
The System OK alarm NO contact is closed.
The System OK alarm NC contact is open.
If connected, the SCADA system has detected the state change of the fail
alarm relay.
Note: Pushing both push-buttons to acknowledge the gas alarm conditions should not
turn off the indicators since the conditions are not cleared.
9.2.4.5 Gas Alarms Cleared
1. Access the submenu Relays/Analog;GasH Relay.
2. Set the parameter RelayMode of this relay to Normal.
3. Access the submenu Relays/Analog;GasHH Relay.
4. Set the parameter RelayMode of this relay to Normal.
5. On the H201Ci-1, verify that:
The two door-mounted push-button indicators (1 and 2) remain lit.
The Alarm 1 (Gas High) indicator (yellow, DS10; item 15 in Figure 4-7) is off.
The Alarm 2 (Gas High-High) indicator (yellow, DS9; item 14 in Figure 4-7) is off.
The System OK indicator (yellow, DS11; item 16 in Figure 4-3) is lit.
The Alarm 1 NO contact is open.
The Alarm 1 NC contact is closed.
The Alarm 2 NO contact is open.
The Alarm 2 NC contact is closed.
The System OK alarm NO contact is closed.
The System OK alarm NC contact is open.
If connected, the SCADA system has detected the state change of both gas
alarm relays.
Note: Pushing both buttons to acknowledge the gas alarm conditions should turn off
the indicators since the conditions have been cleared.