MA-033 Rev. 14.0, 12-Nov-18
Hydran* 201i Instruction Manual
Page 170
1.1.1.10 Battery Voltage Fault Triggers
The parameters pertaining to these alarm conditions are presented in Table 11-9
below and set in the H201Ti’s Service; Battery and SysOK Relay; FaultTrig. Sub-menus
(for explanations, see Chapter 5).
Description
Priority
Alarm Set Point
Fault Trigger
Alarm
Message
Low-Low battery
voltage
Average
Batt.Alr LL
Batt. LL
Low battery voltage
Very Low
Batt.Alr L
Batt. L
Table 11-9: Battery Voltage Fault Triggers
For explanations on the battery, see Section 3.7.
1.1.1.11 Sensor Operation and Connections Fault Triggers
A sensor test is automatically performed on the first and fifteenth days of each
month at midnight, and relevant parameters are recorded in the History; Service file.
The test can also be forced manually (Service; ForceSensor Test command), but the
result is not recorded. In both cases, one of the alarm messages shown in Table 11-10 is
displayed if the sensor fails the test.
Description
Priority
Alarm Set Point
Fault Trigger
Alarm
Message
Replace sensor now
Very High
SensRep Now
Replace Sensor NOW
Cable
a
short
CableShort
Cable
a
open
CableOpen
a: Either one of the following cables (or connectors in the connection link): Sensor, sensor thermistor or
heating plate thermistor.
Table 11-10: Sensor Operation and Connections Fault Triggers