Hydran* 201i Instruction Manual
MA-033 Rev. 14.0, 12-Nov-18
Run all communication cables in flexible or rigid, metallic
conduits for maximum mechanical and electrical protection
Type NEMA 4X steel enclosure; baked enamel; textured white
finish
244.5 x 349.3 x 157.7 mm (9-5/8 x 13-3/4 x 3-3/16 in)
Rated voltage: 100–120 VAC or 200–240 VAC, 50/60 Hz
Rated power: 160 VA maximum
• CISPR 11: Measurement of radiated and conducted emissions
• IEC 60068-2-1: Environmental testing at cold temperature
• IEC 60068-2-2: Environmental testing at dry heat temperature
• IEC 60255-5: Insulation coordination for measuring relays
and protection equipment
• EN 61000-4-2: ESD immunity
• EN 61000-4-3: Radiated electromagnetic field immunity –
radio frequencies
• EN 61000-4-4: Electrical fast transient/burst immunity
• EN 61000-4-5: Surge immunity
• EN 61000-4-6: Immunity to conducted disturbance
induced by radio-frequency fields
• EN 61000-4-8: Power frequency magnetic field immunity
• EN 61000-4-11: Voltage dips, short interruptions and
voltage variations immunity (applicable for ac power
supply only)
• EN 61010-1: Product safety
• Installed: 6.6kg (15lb)
• Shipping: 7.5kg (17lb)
Supports all H201Ti functions plus networking and embedded
software upgrading; available in Microsoft Windows version
Ambient temperature*: -40 to +55˚C (-40 to +131˚F)
Relative humidity: 95% RH, non-condensing
Altitude: up to 2,000m (6,500ft)