MA-033 Rev. 14.0, 12-Nov-18
J.3.1.2 Write (SET or FORCE) Single Coil (05h)
This function is used to set a binary value. Only one binary can be set at a time. The
address to set and the value must be specified. The value will be FF00h to set a binary,
and 0000h to clear it. The return will confirm the address and the value set. Table J - 8
below shows the format of the master and slave packets.
Note: This Section shows how to build and understand a 05h Modbus
request/response exchange. To read or write Hydran 201Ti digital data values, please
refer to the subsequent Sections.
Table J-9 below presents, as an example, the writing (SET) of coil 173 value to “ON”.
Request
Function Code
1 byte
05h
Output Address
2 bytes
0000h to FFFFh
Output Value
2 bytes
0000h or FF00h
Response
Function Code
1 byte
05h
Output Address
2 bytes
0000h to FFFFh
Output Value
2 bytes
0000h or FF00h
Error
Error Code
1 byte
85h
Exception Code
1 byte
01 or 02 or 03 or 04 or 06
Table J - 8: Format for Write (SET or FORCE) Single Coil (05h)
Request
Response
Field Name
(hex)
Field Name
(hex)
Function
05
Function
05
Output Address Hi
00
Output Address Hi
00
Output Address Lo
AC
Output Address Lo
AC
Output Value Hi
FF
Output Value Hi
FF
Output Value Lo
00
Output Value Lo
00
Table J - 9: Writing (SET) of Coil 173 Value to "ON"