Inputs/Outputs (X10), Standard Signals
46 1.10 GB (2019/02/28)
When connecting the applicator to an external controller there are connectors available for inputs and outputs. For
the assignment of these optional connectors see the following sections.
Unused outputs must be insulated before the unit is started up.
Inputs/Outputs (X10), Standard Signals
This optional connection provides inputs/outputs for external control (e.g. PLC).
Pin Designation || I/O || Description || Colour || On circuit board 70039292
1 Status || Out || Printer status || Brown || X30.8
2 Gnd || I/O || Earth (all DC voltages) || Blue || X30.2
3 Ready || Out || Applicator ready || White || X30.3
4 End || Out || End of reel || Green || X30.4
5 Dim || Out || Diminishing reel || Pink || X30.5
6 On || In || Applicator ON (1 – active) || Yellow || X30.6
7 Fault || Out || Applicator fault (including web break) || Black || X30.7
8 Stopdelay* || In || 0–10 V stop delay || Grey || X34.3
9 Adc+10V || Out || +10 V DC for analogue inputs || Red || X34.6
10 Speed* || In || 0–10 V speed || Purple || X34.4
11 Startdelay* || In || 0–10 V start delay || Grey-pink || X34.2
12 Ack || In || Reset malfunction || Red-blue || X30.1
* Notice: The pin should be connected to “GND” if not in use.