EasyManuals Logo
Home>Honeywell>Controller>AUTOMATIC CONTROL

Honeywell AUTOMATIC CONTROL User Manual

Honeywell AUTOMATIC CONTROL
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
PNEUMATIC CONTROL FUNDAMENTALS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
90
PNEUMATIC CONTROL SYSTEM EXAMPLE
The following is an example of a typical air handling system
(Fig. 74) with a pneumatic control system. The control system
is presented in the following seven control sequences (Fig. 75
through 79):
—Start-Stop Control Sequence.
— Supply Fan Control Sequence.
— Return Fan Control Sequence.
—Warm-Up/Heating Coil Control Sequence.
—Mixing Damper Control Sequence.
—Discharge Air Temperature Control Sequence.
—Off/Failure Mode Control Sequence.
Controls are based upon the following system information
and control requirements:
System Information:
—VAV air handling system.
— Return fan.
— 35,000 cfm.
—4,000 cfm outside air.
—3,000 cfm exhaust air.
—Variable speed drives.
—Hot water coil for morning warm-up and to prevent
discharge air from getting too cold in winter .
— Chilled water coil.
—Fan powered perimeter VAV boxes with hot water reheat.
—Interior VAV boxes.
—Water-side economizer.
—8:00 A.M to 5:00 P.M. normal occupancy.
— Some after-hour operation.
GRAVITY
RELIEF
RETURN
AIR
RETURN FAN
SUPPLY FAN
EAST
ZONE
DISCHARGE
AIR
WEST
ZONE
MIXED
AIR
OUTSIDE
AIR
EXHAUST
M10298
Control Requirements:
— Maintain design outside air airflow during all levels of
supply fan loading during occupied periods.
— Use normally open two-way valves so system can heat
or cool upon compressed air failure by manually running
pumps and adjusting water temperatures.
—Provide exhaust/ventilation during after-hour occupied
periods.
— Return fan sized for 35,000 cfm.
START-STOP CONTROL SEQUENCE
Fans 1M through 3M (Fig. 75) operate automatically
subject to starter-mounted Hand-Off-Automatic Switches.
The Supply Fan 1M is started and controls are energized
by Electric-Pneumatic Relay 2EP at 0645 by one of the
following:
— An Early Start Time Clock 1TC
—A drop in perimeter space temperature to 65F at Night
Thermostat TN
— An after-hour occupant setting the Spring-Wound
Interval Timer for 0 to 60 minutes.
The Supply Fan 1M operation is subject to manually reset
safety devices including Supply and Return Air Smoke
Detectors; a heating coil, leaving air, Low Temperature
Thermostat; and a supply fan discharge, duct High Static
Pressure Cut-Out.
Fig. 74. Typical Air Handling System.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL
CategoryController
LanguageEnglish

Related product manuals