PNEUMATIC CONTROL FUNDAMENTALS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
94
DISCHARGE AIR TEMPERATURE
CONTROL SEQUENCE
Any time the AHU (Fig. 79) operates in the non-warm-up
mode, Switching Relay SR-4 operates to allow the normal
Discharge Air Temperature Controller TC-3 to modulate the
hot water valve closed (through Switching Relay SR-1, Fig. 77)
and the chilled water valve open in sequence, on a rising
cooling load, to maintain the Temperature Controller TC-3
setpoint. Controller TC-3 is a PI (proportional plus integral)
controller.
NOTE: In this constant 4000 cfm outside air system, if the
return air is 72F and the outside air is -5F, the mixed
air temperature will drop below 55F if the AHU
airflow drops below 52 percent of the design airflow.
OFF/FAILURE MODE CONTROL
SEQUENCE
If compressed air fails, both control valves open, the outside
air damper closes, and the return air damper opens.
When the fan is off, Switching Relay SR-3 (Fig. 78)
positions to close the hot water valve, Switching Relay SR-5
(Fig. 79) positions to close the chilled water valve, the outside
air damper closes, and the return air damper opens.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL
CategoryController
LanguageEnglish

Related product manuals