118 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Reporting Receivers Compatible with the Control Panel
Fire System Overridden FS 0 FSNN000000 1 245 00 000
Fire System Override Restore FR 0 FRNN000000 3 245 00 000
Ground fault condition trouble YP Exp. ID YPNNXX0000 1 310 Exp. ID 000
Ground fault condition trouble restore YQ Exp. ID YQNNXX0000 3 310 Exp. ID 000
Initial power up RR 0 RRNN000000 1 305 00 000
Local programming aborted or ended
with errors
LU 0 LUNN000000 1 628 00 000
Local programming begin LB 0 LBNN000000 1 627 00 000
Local programming ended normally LS 0 LSNN000000 1 628 00 000
Network node trouble (panel missing) EM Panel ID EMNNNN0000 1 334 Panel ID 000
Network node trouble restore
(panel no longer missing)
EN Panel ID ENNNNN0000 3 334 Panel ID 000
OPG Inhibit Trouble FT Group # + 1000 FTNN001GGG 1 320 00 Group #
OPG Inhibit Trouble Restore FJ Group # + 1000 FJNN001GGG 3 320 00 Group #
OPG Inhibit of Releasing Group SS Group # + 1000 SSNN001GGG 1 203 00 Group #
OPG Inhibit of Releasing Group Restore SR Group # + 1000 SRNN001GGG 3 203 00 Group #
Phone line 1 trouble detected LT 1 LTNN000001 1 351 00 000
Phone line 1 trouble restore LR 1 LRNN000001 3 351 00 000
Phone line 2 trouble detected LT 2 LTNN000002 1 352 00 000
Phone line 2 trouble restore LR 2 LRNN000002 3 352 00 000
Printer is off-line trouble VZ Exp. ID VZNNXX0000 1 336 Exp. ID 000
Printer is off-line trouble restore VY Exp. ID VYNNXX0000 3 336 Exp. ID 000
Printer is out of paper trouble VO Exp. ID VONNXX0000 1 335 Exp. ID 000
Printer is out of paper trouble restore VI Exp. ID VINNXX0000 3 335 Exp. ID 000
Releasing Notif/Control Circuit Disabled pi Exp. ID SS Point # SSNNXXPPPP 1 203 Exp. ID Point #
Releasing Notif/Control Circuit enabled pi Exp. ID SR Point # SRNNXXPPPP 3 203 Exp. ID Point #
Remote programming aborted or ended
with errors
RU 0 RUNN000000 1 413 00 000
Remote programming ended normally RS 0 RSNN000000 1 412 00 000
Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103
Repeater ground fault trouble restore EN 0103 ENNN000103 3 334 Panel ID 103
Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100
Repeater missing trouble restore EN 0100 ENNN000100 3 334 Panel ID 100
Repeater Rx1 communication trouble EM 0101 EMNN000101 1 334 Panel ID 101
Repeater Rx1 communication trouble re-
store
EN 0101 ENNN000101 3 334 Panel ID 101
Repeater Rx2 communication trouble EM 0102 EMNN000102 1 334 Panel ID 102
Repeater Rx2 communication trouble re-
store
EN 0102 ENNN000102 3 334 Panel ID 102
SBUS Class A supervision lost ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS Class A supervision restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SBUS expander trouble ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS expander trouble restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SLC class A supervision trouble ET Exp. ID ETNNXX0000 1 331 Exp. ID 000
SLC class A supervision trouble restore ER Exp. ID ERNNXX0000 3 331 Exp. ID 000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module ID
# (If Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Reporting Formats Table (Continued)

Table of Contents

Other manuals for Honeywell Farenhyt Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt Series and is the answer not in the manual?

Honeywell Farenhyt Series Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt Series
CategoryControl Panel
LanguageEnglish

Related product manuals