IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021 61
Network Programming Network Management
6.2.4 Computer Access
The Installer located at the panel site can initiate the communications between the panel and a computer running the HFSS Honeywell Fire
Software Suite (see also Section 10.5). In order for this communication to function properly, both the computer (running the software) and
the control panel must have matching computer access numbers and computer codes.
To program computer access information, do the following:
1. Enter the Installer Code. The panel will automatically access the Main Menu.
2. Select 6 to access the Network Programming.
3. Press 4 to enter the Computer Access Menu.
4. Enter the Computer Access Number (up to 6-digits), then, press ENTER.
5. Enter the computer code, then press ENTER.
6.2.5 Access Codes
The Access Codes provide the user access to the control panel functions. Each Access Code can be customized for each user. This feature
allows some users the ability to access the programming and other higher level panel functions, while other users may only need access to
the lower level functions (such as, preforming fire drills or acknowledging trouble conditions).
Profile 1 is the profile used that dictates what functions to which the Fire Fighter Key has access. Because this is the profile used for a
key, the User Name and the Access Code cannot be edited for this profile. Table 6.1 lists the Profiles.
Profile 2 is the profile used for the Installer and is referred to as the “Installer Code”. This profile’s user name and panel functions can
not be edited. Table 6.1 lists the panel functions that can be selected for each user profile.
To change an Access Code, do the following.
1. Enter the Installer Code. The panel will automatically access the Main Menu.
2. Select 6 to access the Network Programming Menu.
3. Select 5 to access the Access Codes.
The Display reads: Select Profile 01
Fire Fighter’s Key
4. Press the up or down arrow key to select the Access Code you want to edit.
5. Then, press ENTER.
Type of Function Selectable Functions
Panel Operations System Reset
System Silence
System Ack
Fire Drill Key
*F1 Function Key
*F2 Function Key
*F3 Function Key
*F4 Function Key
Panel Menus System Tests
Fire Drill Menu
Indicator Test
Walk Test-No Report
Walk Test -With Report
Communicator Test
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Single Device Locator
SLC Multiple Device Locator
I/O Point Control
Event History
Set Time & Date
System Information
Network Diagnostics
Network Programming
Panel Programming
Send/Receive Firmware Update
Note: *Function Keys are only available on the RA-2000LCD annunciator.
Table 6.1 User Profile Selectable Panel Functions

Table of Contents

Other manuals for Honeywell Farenhyt Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt Series and is the answer not in the manual?

Honeywell Farenhyt Series Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt Series
CategoryControl Panel
LanguageEnglish

Related product manuals