14 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When you use the carbon monoxide detection, the system must be monitored by a Supervising Station.
2.2.7 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Model/Module Description Local Releasing
Remote
Station
Auxiliary
Central
Station
Emergency
Signaling
IFP-75 Main board Y Y Y Y Y Y
5220 Direct connect module N N N Y N O
5496 NAC expander O Y O O O O
5860 LCD Annunciator O O O O O O
5865 LED Annunciator O O O O O O
5880 LED/I/O Module O O O O O O
RPS-1000 Intelligent Power Module O Y N N N O
RA-1000 LCD Annunciator O O O O O O
RA-2000 LCD Annunciator O O O O O O
SK-NIC Network card O O O O O O
SK-FML/ -FSL Fiber module O O O O O O
IFP-75CB or IFP-75BCB Enclosure Y Y Y Y Y Y
Cell-Mod/Cell-Cab-SK Cellular transmitter O O O O O O
Y = YES, N = NO, O = OPTIONAL
Table 2.1 NFPA Requirements for IFP-75