132 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Appendix A: Compatible Devices
A.1 Notification Appliances
For the proper operation, you must use the polarized devices with a 4.7k ohm EOL resistor on each loop. All supervised
notification appliances used with the fire alarm control panel must be polarized.
Table A.1 lists the notification appliances compatible with the fire alarm control panel. To identify the notification appliances
which can be synchronized and the type of SYNC available, refer to the Audio and Visual columns.
NOTE: Not all devices can use the Sync feature, be sure to check the table below to ensure the device you have chosen will work with this
feature. This control is UL listed for panel wide Synchronization.
Manufacturer Model Audio Visual Type
AMSECO
SH24W-153075
xx
Horn/Strobe
SAD24-153075
x
Strobe
SAD24-75110
x
Strobe
SL24W-75110
x
Strobe
SL24C-3075110
x
Strobe
SLB24-75
x
Strobe
RSD24-153075
x
Strobe
RSD24-75110
x
Strobe
SH24W-75110
xx
Horn/Strobe
SH24W-3075110
xx
Horn/Strobe
SHB24-75
xx
Horn/Strobe
SCM24W-153075
x
Chimes/Strobe
SCM24W-75110
x
Chimes/Strobe
SCM24C-3075110
x
Chimes/Strobe
SCM24C-177
x
Chimes/Strobe
H24W
x
Horn
H24R
x
Horn
FCI
S2415-FC
x
Strobe
S241575-FC
x
Strobe
S2430-FC
x
Strobe
130-3117C
x
Mini Horn
130-3147C
x
Mini Horn
BLV-6
x
Vibrating Bell
BLV-10
x
Vibrating Bell
BLVCH
x
Vibrating Chime
H12/24-FC
x
Horn
H12/24W-FC
x
Horn
H12/24K-FC
x
Horn
HC12/24-FC
x
Horn
Table A.1 Compatible Notification Appliances