Monitoring and Operating the Controller 
4.5.2 Viewing the operating parameters 
Press the LOWER DISPLAY key to scroll through the operating parameters listed in Table 
4-3. The lower display will show only those parameters and their values that apply to 
your specific model. 
Table 4-3  Lower Display Key Parameter Prompts 
Lower Display   Description 
OUT XX.X 
OUTPUT—Output value is shown in percent with one decimal point for all output 
types except Three Position Step Control (TPSC).  For TPSC, when no slidewire is 
connected, this display is an estimated motor position and is shown with no decimal 
point.  For Position Proportional Control, if the slidewire fails, then the instrument 
automatically switches over to TPSC and the OUT display changes with it. 
SP XXXX 
LOCAL SETPOINT #1—Also current setpoint when using SP Ramp. 
2SP XXXX 
LOCAL SETPOINT #2 
3SP XXXX 
LOCAL SETPOINT #3 
RSP XXXX 
REMOTE SETPOINT 
1IN XXXX 
INPUT 1—Used only with combinational input algorithms. 
2IN XXXX 
INPUT 2 
POS  XX 
SLIDEWIRE POSITION—Used only with TPSC applications that use a slidewire input.
CSP XXXX 
COMPUTER SETPOINT—When SP is in override. 
DEV XXXX 
DEVIATION—Maximum negative display is –999.9. 
PIDSET X 
TUNING PARAMETER —where X is either 1 or 2. 
ET HR.MN 
ELAPSED TIME—Time that has elapsed on the Timer in Hours.Minutes. 
OTR HR.MN 
TIME REMAINING—Time remaining on the Timer in Hours.Minutes. The “O” is a 
rotating clock face. 
RAMPXXXM 
SETPOINT RAMP TIME—Time remaining in the Setpoint Ramp in minutes. 
SPN XXXX  SETPOINT NOW—Current Setpoint when SP Rate is enabled.  The SP XXXX display 
shows the “target” or final setpoint value. 
XXRAHR.MN 
RAMP SEGMENT NUMBER AND TIME REMAINING—Set Point Programming 
display. XX is the current segment number and 
HR.MN is the time remaining for this 
segment in Hours.Minutes. 
XXSKHR.MN 
SOAK SEGMENT NUMBER AND TIME REMAINING— Set Point Programming 
display. XX is the current segment number and 
HR.MN is the time remaining for this 
segment in Hours.Minutes. 
RECYC XX 
NUMBER OF SP PROGRAM RECYCLES REMAINING 
To BEGIN 
RESET SP PROGRAM TO START OF FIRST SEGMENT 
RERUN 
RESET SP PROGRAM TO START OF CURRENT SEGMENT 
AUX XXXX 
AUXILIARY OUTPUT—Displayed only when output algorithm is not Current Duplex. 
BIA XXXX 
BIAS—Displays the manual reset value for algorithm PD+MR.  
TUNE OFF 
LIMIT CYCLE TUNING NOT RUNNING—Appears when Accutune is enabled but not 
operating. 
DO FAST 
Limit Cycle Tuning with the objective of producing quarter-damped tuning parameters.  
This tuning may result in PV overshoot of the SP setting. 
DO SLOW 
Limit Cycle Tuning with the objective of producing damped or Dahlin tuning 
parameters, depending upon the detected process deadtime.  The tuning parameters 
calculated by this selection are aimed at reducing PV overshoot of the SP setting. 
12/04  UDC3200 Universal Digital Controller Product Manual  101