Troubleshooting/Service 
Lower 
Display 
Reason for Failure  How to Correct the Problem 
CONF ERR 
• PV low limit is > PV high limit 
• SP low limit is > SP high limit 
• Output low limit > Output high limit  
 
PV LIMIT 
PV out of range. 
PV = INP1 x RATIO1+ INP1 BIAS 
1.  Make sure the input signal is correct. 
2.  Make sure the Ratio and Bias settings are correct. 
3.  Recheck the calibration. Use Bias of 0.0 
RV LIMIT 
The result of the formula shown below is 
beyond the range of the remote variable. 
RV = INP2 X RATIO + BIAS 
1.  Make sure the input signal is correct. 
2.  Make sure the Ratio2 and Bias2 settings are 
correct. 
3.  Recheck the calibration. Use a Ratio2 of 1.0 and a 
Bias2 of 0.0. 
SEGERR 
Setpoint Program start segment number is 
less than ending segment number. 
Check SP Program configuration, subsection 3.5 Set 
up Group SPPROG function prompts “STRSEG” and 
“ENDSEG”. 
CAL MTR 
Slidewire calibration never performed.  Field Calibrate the slidewire.  See Section 6.4. 
SW FAIL 
Position Proportional slidewire input failure. See the Trouble Shooting Procedure in Section 7.7. 
SOOTING 
Percent Carbon falls outside sooting 
boundary 
Check process for correct operation. 
TCx WARN 
Thermocouple on Input x (1 or 2)  is 
starting to burnout. 
This diagnostic message means that the controller 
has detected that the thermocouple is starting to 
burnout. This error message may also be created if 
the resistance of the wires used to connect the 
thermocouple to the instrument is above 100 ohms. 
TCxFAIL 
The Thermocouple on Input x (1 or 2) is in 
imminent danger of burning out. 
This diagnostic message means that the controller 
has detected that the thermocouple will soon fail. User 
should consider replacing the thermocouple as soon 
as possible. This message will also be generated if the 
resistance of the wires used to connect the 
thermocouple to the instrument is above 180 ohms. 
CURFAIL 
Current Output is less than 3.5 mA.  The current output is open circuit. Check the field 
wiring. See Procedure #2. 
AXFAIL 
Auxiliary Output is less than 3.5 mA.  The auxiliary output is open circuit. Check the field 
wiring. See Procedure #9. 
1.  Check the configuration for each item and 
reconfigure if necessary. 
7.6  Controller Failure Symptoms 
Introduction 
In addition to the error message prompts, there are failure symptoms that can be 
identified by noting how the controller displays and indicators are reacting. 
Symptoms 
Compare your symptoms with those shown in Table 7-4. 