Monitoring and Operating the Controller 
Switch between two sets via keyboard (without automatic switch-over) 
Table 4-18  Procedure for Switching PID SETS from the Keyboard  
Step  Operation  Press  Result 
1 
Select Control  
Set-up Group 
Lower
Display
Lower
Display
Lower
Display
 
Until you see: 
Upper Display = (the PV value) 
Lower Display = PIDS X  (X= 1 or 2) 
2 
 
or  
To change PID SET 1 to PID SET2 or Vice Versa. 
You can use Accutune on each set. 
3 
 
Lower
Display
Lower
Display
Lower
Display
 
To accept changes. 
4.13   Alarm  Setpoints 
Introduction 
An alarm consists of a relay contact and an operator interface indication. The alarm relay 
is de-energized if setpoint 1 or setpoint 2 is exceeded. 
The alarm relay is energized when the monitored value goes into the allowed region by 
more than the hysteresis. 
The relay contacts can be wired for normally open (NO) energized or normally closed 
(NC) de-energized using internal jumper placement. See Table 2-3 in the Section 2 – 
Installation for alarm relay contact information. 
There are four alarm setpoints, two for each alarm. The type and state (High or Low) is 
selected during configuration. See Subsection 3.13 – Configuration for details. 
118  UDC3200 Universal Digital Controller Product Manual  12/04