Installation 
 
Configure:
2S1TY = NONE
 
2S2TY = NONE
 
2 Wire Transmitter
 
 
+
 
INPUT 1OUTPUT 3
 
250 
26 +
27 -
5 +
 
6 - 
If necessary, install a zener diode here to reduce voltage at the 
transmitter.  A 1N4733 will reduce the voltage at the transmitter to 
approximately 25 Vdc.
 
1
 
1
 
 
Figure 2-18 Transmitter Power for 4-20 mA — 2 wire Transmitter Using Open 
Collector Alarm 2 Output 
 
 
2 Wire Transmitter
 
 
+
 
INPUT 1
UXILIARY OUTPUT
 
250 
26 +
27 -
12 + 
13 - 
Configure:
        AUXOUT = OUT
 
uxiliary Output Calibration
 
        ZEROVAL = 16383
 
        SPANVAL = 16383
 
If necessary, install a zener diode here to reduce voltage at the 
transmitter.  A 1N4733 will reduce the voltage at the transmitter to 
approximately 25 Vdc.
 
1
 
1
 
 
 
Figure 2-19 Transmitter Power for 4-20 mA — 2 Wire Transmitter  
Using Auxiliary Output 
 
12/04  UDC3200 Universal Digital Controller Product Manual  35