Installation
20
21
5
6
Control Relay #1
Motor
Power
Supply
Close (CCW)
Open (CW)
Control Relay #2
xxxx
A
larm #2 is not available with this configuration.
1
L1/Hot
L2/N
2
2
See Input 2 Wi
ring Diagram for Slidewire Connections.
1
3
Electromechanical Relays are rated at 5 amps at 120 Vac or 240 Vac
or 24 Vdc. Solid State Relays are rated at 1 Amp at 25
°C and
derated linearly to 0.5 Amps at 55
°C. Customer should size fuses
accordingly. Use Fast Blo fuses only.
Figure 2-13 Position Proportional or Three Position Step Control
Connections w/o Dual Relay Option
19
20
21
Motor
Power
Supply
Close (CCW)
Open (CW)
Control
Relay #1
Control
Relay #2
L2/N
L1/Hot
A
larm #2 is available with with this configuration.
2
Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or
30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.
2
xxxx
See Input 2 Wiring Diagram for Slidewire Connections.
1
3
Figure 2-14 Position Proportional or Three Position Step Control
Connections with Dual Relay Option