Input Calibration
5.4.2 Thermocouple Inputs Using a Thermocouple Source
Refer to Figure 5-3 and wire the controller according to the procedure given in Table 5-4.
Table 5-4 Set Up Wiring Procedure for Thermocouple Inputs using
Thermocouple Source
Step Action
1
Connect the thermocouple extension wires to the terminals for Input #1 as shown in
Figure 5-3.
XXXX
Thermocouple
Source
Thermocouple
Extension Wire
+
_
26 +
27 -
25
23 +
24 -
22
Input 1
Input 2
Figure 5-3 Wiring Connections for Thermocouple Inputs Using
Thermocouple Source
5.4.3 RTD Inputs
Refer to Figure 5-4 and wire the controller according to the procedure given in Table 5-5.
Table 5-5 Set Up Wiring Procedure for RTD Inputs
Step Action
1
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-4.
XXXX
Decade
Resistance
Box
Copper Leads
Equal Length
26 +
27 -
25 R
23 +
24 -
22 R
Input 1
Input 2
Figure 5-4 Wiring Connections for RTD (Resistance Thermometer Device)