Output Calibration 
Procedure 
The procedure for calibrating the Current Output is listed in Table 6-2. Make sure LOCK 
in the Tuning Set Up group is set to NONE. (See Subsection 3.4 – Tuning Set Up Group.) 
Table 6-2  Current Output Calibration Procedure  
Step  Operation  Press  Result 
1 
Enter Calibration 
Mode 
SetupSetup
 
until you see
Upper Display = CALIB 
Lower Display = CURRENT 
2 
Calibrate 0 % 
Function
FunctionFunction
 
You will see: 
Upper Display = A Value 
Lower Display = ZERO VAL 
 
 
or  
 
 
 
Until the desired 0 % output is read on the milliammeter, 
use the values shown below depending on the action of 
your controller.  Normally, this will be the setting that 
produces 4 mA. 
3 
Calibrate 100 % 
Function
FunctionFunction
 
This stores the 0 % value and  
you will see: 
Upper Display = 
A Value 
Lower Display = SPAN VAL 
 
 
or  
 
 
 
Until the desired 100 % output is read on the milliammeter, 
use the values shown below depending on the action of 
your controller. Normally, this will be the setting that 
produces 20 mA. 
4 
Function
FunctionFunction
 
The controller stores the span value. 
 
Exit the 
Calibration Mode 
Lower
Display
Lower
Display
Lower
Display
 
To exit the calibration mode. 
 
12/04  UDC3200 Universal Digital Controller Product Manual  145