Modbus Read, Write and Override Parameters plus Exception Codes 
10.7.10 Communications 
Table 10-18 lists all the register addresses and ranges or selections for the function 
parameters in Set-up Group Communications.  
Table 10-18  Set-up Group – Communications 
Parameter 
Description 
Register 
Address 
Data 
Type 
Data Range or 
Enumerated Selection 
  Hex  Decimal     
Shed Time  004F  79  INT  R/W  0 = No Shed 
1 = 255 sample periods 
00A2 162  R/W 
0 = Last Mode and Last Output 
2 = Manual Mode, Failsafe Output 
3 = Automatic Mode 
Shed Setpoint 
Recall 
00A3  163  INT  R/W  0 = To Last Local Setpoint used 
1 = CSP 
005A 90  FP  R/W  –20.00 to 20.00 
Computer 
Setpoint Bias 
005B 91  FP  R/W  –999 to 9999. 
Communication
Address 
004D  77  FP  R/W  1 - 99 
Communications 
Type 
00E7 231  INT R/W 
0 = None 
1 = Disable 
2 = RS-485 Modbus 
3 = Ethernet 
IR Port Enable  00F1  241  INT  R/W  0 = Disable 
1 =- Enable 
Baud Rate  00E8  232  INT  R/W  0 = 4800 
1 = 9600 
2 = 19200 
3 = 38400 
Transmit Delay  004E  78  FP  R/W  Response Delay in ms 
(1 to 500) +6ms 
Floating Point 
Byte Order 
00E9  233  INT  R/W  0 = Big Endian 
1 = Big Endian Byte Swap 
2 = Little Endian 
3 = Little Endian Byte Swap 
Shed Enable  00EA  234  INT  R/W  0 = Enable 
1 = Disable 
009A  154  R/W  0 = No Shed 
Comm Data 
Units 
00A1  161  INT  R/W  0 = Percent 
1 = Engineering Units 
Access 
 
Shed Mode and 
Output 
INT 
1 = Manual Mode, Last Output 
Computer 
Setpoint Ratio 
Shed Time  INT 
1 = 255 sample periods 
12/04  UDC3200 Universal Digital Controller Product Manual  215