EasyManua.ls Logo

Honeywell UDC3200 - Setpoint Rate; Setpoint Ramp

Honeywell UDC3200
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monitoring and Operating the Controller
RUN/HOLD key
You can start or stop the Ramp or Program using the RUN/HOLD key.
4.18 Setpoint Rate
Introduction
When you have configured a SETPOINT RATE, it will apply immediately to local
setpoint change.
Configuration check
Make sure:
SPRATE is enabled
A Rate Up (EUHRUP) or Rate Down (EUHRDN) value has been configured in
Engineering units per hour.
ATTENTION
A value of 0 will imply an immediate change in setpoint, that is, NO RATE applies. See
Subsection 3.5 – Configuration group “SPRAMP” for details.)
Operation
When a change to local setpoint is made, this controller will ramp from the original
setpoint to the “target” setpoint at the rate specified.
The current setpoint value is shown as SPn XXXX on the lower display while the
“target” setpoint is shown as SP XXXX on the lower display.
Power outages
If power is lost before the “target” setpoint is reached, upon power recovery, the
controller powers up with Sn = Current PV value and it automatically “Restarts” from Sn
= current PV value up to the original “target” setpoint.
4.19 Setpoint Ramp
Introduction
When you have configured a SETPOINT RAMP, the ramp will occur between the
current local setpoint and a final local setpoint over a time interval of from 1 to 255
minutes. You can RUN or HOLD the ramp at any time.
Configuration Check
Make sure
SPRAMP is enabled
SP RATE and SPPROG are not running.
12/04 UDC3200 Universal Digital Controller Product Manual 123

Table of Contents

Related product manuals