Honeywell UDC3200 - Read Software Options Status; Table 10-1 Control Data Parameters; Table 10-2 Option Status; Figure 10-1 Software Option Status Information

Honeywell UDC3200
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-1 Control Data Parameters
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Input #1 007B 123 FP RD In Engineering Units or
Percentage
Input #2 007C 124 FP RD In Engineering Units or
Percentage
PV, SP, Output 007A 122 FP RD In Engineering Units or
Percentage
10.3 Read Software Options Status
Read
Doing a Read of register address 00B9 listed in Table 10-2 will tell you which of the
available options are enabled / installed or disabled / not installed.
Table 10-2 Option Status
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Option Status
(Read only)
00B9 185 INT RD
See Figure 1 -1. 0
The data field in the response message will be a decimal number from 0 to 255. Convert
the decimal number to binary as shown in Figure 1 .to determine which options are or
are not active.
0-1
0 to 255
Convert decimal to binary
Math
0
=
not installed
1
=
installed
EXAMPLE:
2
Binary
SP Programming
installed
0
0
0
0
0
1
1
0
SP Programming
0 to 255
Convert decimal to binary
Math
0
=
not installed
1
=
installed
EXAMPLE:
Binary
SP Programming
installed
0
0
0
0
0
1
1
0
EXAMPLE:
Binary
SP Programming
installed
0
0
0
0
0
0
1
0
SP Programming
Figure 10-1 Software Option Status Information
12/04 UDC3200 Universal Digital Controller Product Manual 187