Configuration 
3.5  SP Ramp Set Up Group 
Introduction 
Set Point Ramp, Set Point Programs and Set Point Rates can be configured in this group. 
A single Setpoint Ramp [SP RAMP] can be configured to occur between the current local 
setpoint and a final local setpoint over a time interval of from 1 to 255 minutes.  
A Set Point Rate [SPRATE] lets you configure a specific rate of change for any local 
setpoint change. 
A single Set Point Program [SP PROG] with up to 12 segments can be configured. 
For more information on Set Point Rate, Ramp and Programming, see Sections 4.17 
through 4.20. 
You can start and stop the ramp/program using the 
RUN/HOLD key. 
PV Hot Start is a configurable feature and means that, at initialization, the setpoint is set 
to the current PV value and the Ramp or Rate or Program then starts from this value. 
Function Prompts 
Table 3-5  SPRAMP Group Function Prompts 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
SP RAMP 
SP Program must be 
disabled for SP Ramp 
prompts to appear 
 
 
 
 
SINGLE SETPOINT RAMP—Make a selection to 
enable or disable the setpoint ramp function. Make 
sure you configure a ramp time and a final setpoint 
value. 
SP Programming must be disabled. 
 
DISABLE 
 
ENABLE 
DISABLE SETPOINT RAMP—Disables the setpoint 
ramp option. 
ENABLE SETPOINT RAMP—Allows the single 
setpoint ramp prompts to be shown. 
TIME MIN 
0 to 255 minutes 
SETPOINT RAMP TIME—Enter the number of 
minutes desired to reach the final setpoint. A ramp 
time of “0” implies an immediate change of setpoint. 
44  UDC3200 Universal Digital Controller Product Manual  12/04