Configuration 
3.13   Communications  Group 
Introduction 
The Communications group lets you configure the controller to be connected to a host 
computer via Modbus® or Ethernet TCP/IP protocol. 
Introduction 
A controller with a communications option looks for messages from the host computer. If 
these messages are not received within the configured shed time, the controller will 
SHED from the communications link and return to stand-alone operation. You can also 
set the SHED output mode and setpoint recall, and communication units. 
Up to 99 addresses can be configured over this link. The number of units that can be 
configured depends on the link length, with 31 being the maximum for short link lengths 
and 15 drops being the maximum at the maximum link length.  
Function Prompts 
Table 3-13 Communications Group Function Prompts 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
Com ADDR 
1 to 99 
COMMUNICATIONS STATION ADDRESS—This is 
a number that is assigned to a controller that is to be 
used with the communications option. This number 
will be its address. 
ComSTATE 
 
COMMUNICATIONS SELECTION 
 
DISABLE 
DISABLE—Disables RS-485 communications 
option. 
 
MODBUS 
MODBUS—Enables RS-485 Modbus RTU 
communication port. 
IR ENABLE 
DISABLE 
ENABLE 
IR ENABLE–Disable/Enables IR communications 
port. 
 ATTENTION  If there are no IR communications 
transactions for four minutes, then the IR port 
automatically shuts down.  It can be re-enabled by 
pressing any key on the front panel. 
BAUD 
 
 
 
4800 
9600 
19200 
38400 
BAUD RATE is the transmission speed in bits per 
second.  This value is used for both RS-485 and IR 
Communications, but for IR Communications, values 
below 19200 baud are interpreted as being 19200 
baud. 
4800 BAUD 
9600 BAUD 
19200 BAUD 
38400 BAUD 
84  UDC3200 Universal Digital Controller Product Manual  12/04