Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
 
Lo FIRE 
LOW FIRE—Contact closure forces the loop to 
Manual mode with the output set to the Output Low 
Limit configuration. MAN lights and the Output value 
is shown on the lower display. Opening the switch 
has no effect.  
 ATTENTION  Does not apply to Three Position 
Step Control. 
 
MAN LAT 
MANUAL LATCHING—Contact closure transition 
forces the loop to Manual mode. Opening the switch 
has no effect. If the MAN/AUTO key is pressed while 
the switch is closed, the loop will return to Automatic 
mode. 
 
PV Hold 
PROCESS VARIABLE HOLD—when the switch is 
closed, PV is frozen at last value. When switch 
opens, PV resumes. 
DIG 1COMB 
 
DIGITAL INPUT 1 COMBINATION SELECTIONS 
—This selection allows the specified function to 
occur in addition to the one chosen for DIG IN 1. 
 
DISABLE 
DISABLE—Disables combination function. 
 
+PID2 
PLUS PID2—Contact closure selects PID Set 2. 
 
+TO DIR 
PLUS DIRECT ACTION—Contact closure selects 
direct controller action. 
 
+TO SP2 
PLUS SETPOINT 2—Contact closure puts the 
controller into setpoint 2. 
 
+DIS AT 
PLUS DISABLE ADAPTIVE TUNE—Contact 
closure disables Accutune process.  
 
+TO SP1 
PLUS SETPOINT 1—Contact closure puts the 
controller into setpoint 1. 
 
+RUN 
PLUS RUN SETPOINT PROGRAM/RAMP—
Contact closure starts SP Program/Ramp if enabled. 
DIG INP2 
Same selections as for 
Digital Input 1 
DIGITAL INPUT 2 SELECTIONS 
DIG2COMB 
Same selections as Digital 
Input 1 Combinations 
DIGITAL INPUT 2 COMBINATIONS 
 
12/04  UDC3200 Universal Digital Controller Product Manual  83