Modbus Read, Write and Override Parameters plus Exception Codes 
10.7.6 Input 1 
Table 10-14 lists all the register addresses and ranges or selections for the function 
parameters in Set-up Group Input 1. 
Table 10-14  Set-up Group – Input 1 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
  Hex  Decimal      
Input 1 Type  00A8  168  INT  R/W 
1 = B TC 
2 = E TC H 
3 = E TC L 
4 = J TC H 
5 = J TC M 
6 = J TC L 
7 = K TC H 
8 = K TC M  
9 = K TC L 
10 = NNM H 
11 = NNM L 
12 = Nicrosil H TC 
13 = Nicrosil L TC 
14 = R TC 
15 = S TC 
16 = T TC H 
17 = T TC L 
18 = W TC H 
19 = W TC L 
20 = 100 PT RTD 
21 = 100 PT LO RTD 
22 = 200 PT RTD 
23 = 500 PT RTD 
24 = Radiamatic RH 
25 = Radiamatic RI 
26 = 0-20 mA 
27 = 4-20 mA 
28 = 0-10 mV 
29 = 0-50 mV 
30 = 100 mV 
31 = 0-5 Vdc 
32 = 1-5 Vdc 
33 = 0-10 Vdc 
34 = Unused 
35 = Carbon 
36 = Oxygen 
37 = Thermocouple Differential 
  ATTENTION 
  Changing the Input Type will result in the loss of Field Calibration 
values and will restore the Factory Calibration values. 
12/04  UDC3200 Universal Digital Controller Product Manual  203