Introduction
Slowtune will minimize overshoot, but it will take more time for the process temperature
to reach the target setpoint.
Heat/Cool (Duplex Tune) will automatically tune both the heating and cooling sides of
the process.
Fuzzy Logic - This standard feature uses fuzzy logic to suppress process variable
overshoot due to SP changes or externally induced process disturbances. It operates
independently from Accutune III tuning. It does not change the PID constants, but
temporarily modifies the internal controller response to suppress overshoot. This allows
more aggressive tuning to co-exist with smooth PV response. It can be enabled or
disabled depending on the application or the control criteria.
1.2 Operator Interface
Figure 1-1 UDC3200 Operator Interface
12/04 UDC3200 Universal Digital Controller Product Manual 5