Monitoring and Operating the Controller 
Operation 
The Accutune III algorithm provides user-friendly, on-demand tuning in this controller.  
No knowledge of the process is required at start-up.  The operator simply initiates the 
tuning while in the automatic mode. 
Once Accutune III has been enabled in the TUNE setup group, either “SLOW” or 
“FAST” tuning may be used.  Which one is used is selected via the lower display during 
normal operation. 
For the SLOW selection, the controller calculates conservative tuning constants with the 
objective of minimizing overshoot.  If the controller determines that the process has 
appreciable dead time, it will automatically default to use Dahlin Tuning, which produces 
very conservative tuning constants.  The SLOW selection may be useful for TPSC and 
Position Proportional applications, as it reduces “hunt” problems for the motor.  This 
selection is also recommended for applications that have significant deadtimes. 
For the FAST selection, the controller calculates aggressive tuning constants with the 
objective of producing quarter damped response.  Depending upon the process, this 
selection will usually result in some overshoot.  For this reason, it may be desireable to 
enable the FUZZY tune selection. See Section 4.11. When Fuzzy tune is enabled, it will 
work to suppress or eliminate any overshoot that may occur as a result of the calculated 
tuning parameters as the PV approaches the setpoint. This selection is best suited for 
processes with a single lag or for those that do not have any appreciable deadtime.  
FUZZY tuning does not work well for processes that have appreciable deadtime. 
The Accutune III tuning process will cycle the controller’s output two full cycles 
between the low and high output limits while allowing only a very small Process 
Variable change above and below the SP during each cycle. A “T” shows in the upper 
display until tuning is completed. 
At the end of the tuning process, the controller immediately calculates the tuning 
constants and enters them into the Tuning group, and begins PID control with the correct 
tuning parameters.  This works with any process, including integrating type processes, 
and allows retuning at a fixed setpoint. 
4.10.1  Tune for Simplex Outputs 
After “TUNE” has been enabled, you can start Accutune as shown in Table 4-10.   
Table 4-10  Procedure for Starting “TUNE” 
Step  Operation  Press  Result 
1 
Configure LSP1 
Lower
Display
Lower
Display
Lower
Display
 
Until SP (Local Setpoint 1) shows 
in the lower display. 
2 
 
or  
Until LSP1 is to the desired value. 
3 
Switch to 
“Automatic” Mode 
Man
Auto
Man
Auto
Man
Auto
 
Until the “A” indicator is lighted (on 
controllers with Manual option). 
110  UDC3200 Universal Digital Controller Product Manual  12/04