Monitoring and Operating the Controller 
4.5.3 Diagnostic Messages 
The UDC3200 performs background tests to verify data and memory integrity. If there is 
a malfunction, a diagnostic message will be shown on the lower display. In the case of 
more than one simultaneous malfunction, only the highest priority diagnostic message 
will be displayed. Table 4-4 shows the error messages in order by priority. If any of these 
diagnostic messages appear on the lower display, refer to Section 7 - Troubleshooting for 
information on how to correct the problem. 
Table 4-4 Diagnostic Messages 
Prompt  Description 
EE FAIL 
Unable to write to nonvolatile memory.  A subsequent successful write to 
nonvolatile memory removes this message. 
FAILSAFE 
This error message appears whenever the controller goes into a failsafe 
mode of operation. Failsafe operation occurs when an analog input fails or 
when configuration is corrupted. 
INP1FAIL 
Two consecutive failures of input 1 integration or input value is outside of 
Out-of-Range limits. 
INP2FAIL 
Two consecutive failures of input 2 integration or input value is outside of 
Out-of-Range limits. 
SW FAIL 
Slidewire input failure. Position Proportional Control automatically switched 
to Three Position Step Control. 
CONF ERR 
Configuration Errors—Low limit greater than high limit for PV, SP, Reset, or 
Output. 
SOOTING 
Carbon Potential Problem—Percent Carbon outside of “sooting boundary.” 
IN1 RNG 
Input 1 Out-of-Range—Input is outside of the High or Low Limits. 
 Out-of-range criteria: 
    Linear range: ± 10 % 
    Characterized range: ± 1 % 
IN2 RNG 
Input 2 Out-of-Range—Same criteria as Input 1. 
PV LIMIT 
PV beyond limits—PV outside of PV Hi/Low Limits. 
   PV = (PV source x PV source ratio) + PV source bias 
FAILSAFE 
Failsafe—Check inputs or configuration. 
RV LIMIT 
Remote Variable beyond limits—RSP outside of SP Hi/Low Limits. 
RV = (RV source x RV source ratio) + RV source bias 
SEG ERR 
Segment Error—SP Program starting segment number is less than ending 
segment number. 
CAL MTR 
Slidewire not calibrated. Perform Slidewire calibration. 
SW FAIL 
Position Proportional slidewire input failure. 
TC1 WARN 
The Thermocouple on Input 1 is starting to burnout. 
TC2 WARN 
The Thermocouple on Input 2 is starting to burnout. 
TC1 FAIL 
Thermocouple on Input 1 is in imminent danger of burning out. 
102  UDC3200 Universal Digital Controller Product Manual  12/04