Monitoring and Operating the Controller
Set up Procedure
The following procedure (Table 4-17) to:
select two sets,
set the switch-over value,
set tuning constant value for each set.
Table 4-17 Set Up Procedure
Step Operation Press Result
1
Select Control
Set-up Group
SetupSetup
Until you see:
Upper Display = SET
Lower Display = CONTRL
2
Select PID SETS
Function
FunctionFunction
Until you see:
Upper Display = (available selections)
Lower Display = PID SETS
3
Select PID SETS
Function
or
To select the type of function. Available selections are:
1 ONLY—1 set of constants
2KEYBD—2 sets, keyboard selectable
2PV SW—2 sets, auto switch at PV value
2SP SW—2 sets, auto switch at SP value
4
Set Tuning
Values for Each
Set
Refer to “TUNING” Set up group, subsection 3.4 and set the
following tuning parameters:
PB or GAIN *
RATE MIN *
RSET MIN or RSET RPM *
CYC SEC or CYC SX3 *
PB2 or GAIN2 **
RATE2MIN **
RSET2MIN or RSET2RPM **
CYC2SEC or CYC2SX3 **
*PIDSET1 will be used when PV or SP, whichever is
selected, is greater than the switchover value.
**PIDSET2 will be used when PV or SP, whichever is
selected, is less than the switchover value.
5
Set Switchover
Value for
2 PVSW or
2 SPSW
Selection
Function
FunctionFunction
Until you see:
Upper Display = (the switchover value)
Lower Display = SW VAL
or
To select the switchover value in the upper display.
12/04 UDC3200 Universal Digital Controller Product Manual 117